Building Department and Zoning Enforcement
Tips for Code Compliance
Residential Builders
Michigan Residential Code 2006
No information sheet such as this can substitute
for a thorough knowledge of the Building Code,
however it may be helpful to know the areas where
most commonly found problems occur. The code
sections cited are Michigan Residential Code 2006.
Building Planning
- Foam plastic shall be separated from the
interior of a building by an approved thermal
barrier (2
" drywall or equivalent), attics and crawl
spaces only require
d
"(this includes foam insulation baffles in
attic). Sections R-314.5.2 AND R-314.5.4
- A kitchen, storage room, laundry room,
or bathroom can have a CEILING HEIGHT OF 7', but
for either present or future HABITABLE rooms,
whether basements or any other part of a
dwelling, ceiling height cannot be less than 7'
BETWEEN FINISHED floor and FINISHED ceiling.
This 7' minimum requirement applies to at least
50% of the total area of rooms with partly
SLOPED ceilings. The ceiling height in basements
without habitable spaces may be not less than
6'8" clear except for under beams, girders,
ducts or other obstructions where the clear
height shall be 6'4". Sections R-305.1
- All habitable rooms, or those to be
occupied must have a WINDOW GLASS AREA of at
least 8% of the total floor area (light
requirement) with at least
2
operable (ventilation requirement), or an
alternate mechanical ventilation system.
Sections R-303.1
- Bathrooms must be equipped with a
mechanical vent fan. All fans and vents must
vent directly to the outside. Sections R-303.3
- SLEEPING ROOMS & BASEMENTS WHETHER HABITABLE
OR NOT, must comply with item 3, but, also have
an EMERGENCY EGRESS opening of 5'7" sq. ft.,
(5'0" if grade level). The minimum clear opening
must be at least 20" wide and at least 24" high
and the clear open space (sill) can be no higher
than 44" above the finished floor. An exterior
door within the room can be considered an
emergency egress opening. Sections R-310
- UNDER STAIR PROTECTION - Enclosed
accessible space under stairs shall have walls
and soffits on enclosed side with
2
"drywall. Sections R-311.2.2
- A solid wood door not less than 1 3/8" thick
or equivalent, without glass, is required
between a house and attached garage. A garage
shall be completely separate from the residence
and its attic by
2
"drywall or equivalent on garage side. Sections
R-309.1 & R-309.2
- STAIRWAYS - The greatest riser height
(maximum 83
") within any flight of stairs shall not exceed
the smallest by more than
d ".
Minimum tread width is 9". Stairways shall not
be less than 3' in clear width and shall have a
minimum 6'8" headroom from top of tread to
finished ceiling. Sections R-311.5.1, R-311.5.2,
R-311-5.3.1, R-311.5.3.2
- Garage floor must be installed so as
to prevent the flow of liquids through doorways
into the adjoining dwelling. Sections R-309.3
- Ground fault interrupters (GFI) are
required for electrical protection on bathrooms,
kitchens, exterior outlets and outlets in
garages and basements. Bedrooms shall be
protected by an arc-fault circuit interrupter
for each branch circuit. Sections National
Electrical Code 210.8 & E3802.11
- Maintain 6" of CLEARANCE between the
bottom edge of the siding and top of the final
grade below. (Driveway, sidewalk, patio slab,
top of the sod or landscape bark.) Sections
R-404.1.6. & R-323.1
- SLOPE all final grades away from the
building for drainage with a minimum fall of 6"
within the first 10' or minimum 6" to lot line.
SectionsR-401.3
- SMOKE DETECTORS are required on each
floor immediately adjacent to all sleeping
areas, and in any basement. In new construction,
all detectors shall be wired together and
receive their power from the building wiring.
Sections R-313.2
Foundation:
- Location - Check closely to be sure
the location of your footing forms are in
accordance with the site plan that you submitted
for a building permit.
- Depth - Footings must rest on
undisturbed soil below the frost line. (42"
below finished grade, as measured at a distance
of 6' from the building in the State of
Michigan). Sections R-403.1.4
- Anchorage -
2
"anchor bolts, 6' O.C., 7" into concrete, (or
15" into block) and not more than 12" from a
corner are required in the top of the foundation
wall for the purpose of securing the sill. An
approved alternative is galvanized straps, IF
installed according to manufacturer=
s specifications. Sections R-403.1.6
- Damp Proofing/Water Proofing - Damp
proofing of exterior foundation walls enclosing
basements below grade is required. Water
proofing is required on foundation walls located
below grade which enclose habitable rooms. See
code for specific requirements based on
foundation type and space use. Footing lip must
be clean before tarring. Sections R-406.1 &
R-406.2
- Crawl spaces must be vented on all
walls within 3' of each corner. An access crawl
hole 18" x 24" shall be provided under floor
spaces. Sections R-408.1, R-408.2 & R-408.4
Rough In
- Headers - 2x headers of appropriate size
for the span are required in ALL exterior walls,
as well as any interior load-bearing partitions.
Support is required at each end. (See span table
for specs.) Sections Table R-502.5(1)
- Fire Blocking - Fireblocking of 23/32"
plywood, 2" nominal lumber or
: "
type 2M particle board shall be provided to cut
off all concealed draft openings, such as occur
at bulkheads, soffits, drop ceilings, spaces
between stair stringers, at the top and bottom
of run to form a fire barrier between stories,
boxed-in hoist runs, chimney chase, top and
bottom of furring strips (basement), and between
a top story and roof space. Sections R-602.8
- Corner Bracing - Exterior and foundation
wall panels of frame construction shall be
braced with approved structural sheathing 1"x4"
let-in braces, or approved metal strap devices.
Sections R-602.10.3
- Treated Wood is required at the following
locations:
- Joists within 18" of exposed ground, girders
within 12" of exposed ground, sills on masonry
and within 8" of exposed ground, siding &
sheathing with 6" of exposed ground, all wood in
direct ground contact, all wood girders ending
in exterior masonry walls having less than
2 "
clearance on any side. Sections R-324
- Rafter/Joist Notching - Notching at the
ends of the rafter or ceiling/floor joist shall
not exceed 3
th of the depth. Notches in the top or bottom of
the joists shall not exceed 1/6th of the depth.
Bored holes shall not be within 2" of the top
and bottom and their diameter shall not exceed
a rd
the depth of the member. If plates are cut more
than 50% of its width, a 24 gauge steel metal
angle is required spanning the studs. Sections
R-502.8, R-802.7 & R-602.6.1
- All made up beams (Ex. 3-2 x 10"s) must
have the ends of all splices located on support
posts and held together with 16d 32" O.C. at the
top and bottom, and 2-20d staggered at the end
of each splice. Sections R-502.6 & TABLE 602.7
- Basement POSTS must be fastened to the
floor and the beam above. The screw end down and
prevented from moving. Sections R-407.3
- Double Floor Joists, as required next to
framed openings, under bearing wall partitions,
or any concentrated load bearing areas above
freezers, hot tubs, etc.). Joist Headers around
floor openings must be doubled if 4' or longer
and corner fasteners used for any of 6' or
longer. Any joist (deck included) must have at
least 12
" of end support or be in approved hangers.
Hangers must be installed with the correct nails
in all provided holes. Sections R-502.6.2,
R-502.4 & FIGURE R-502.2
- Joist Hangers - Where joist hangers are used,
they must be of an appropriate size for the width of
the joist and securely fastened to the header and
the tail end of the joist. All nail holes in all
joist hangers must be filled with the nail of the
appropriate size. Refer to manufacturer
s specifications for the proper size nails and other
installation instructions. Sections R-802.9
- Provide a 22" x 30" ACCESS into all attic and
concealed areas over 30" in height. Use fire rated
covers with tight joints. Sections R-807.1
- Chimneys must top out at least 24" above any
roof within 10' but not less than 3' above the point
where the chimney passes through the roof. Sections
R-1003.9
- Rafters resting on another rafter or roof
section must bear on a 2X board over the roof below.
The lower roof, or trusses beneath, must be rated to
carry that extra dead load placed above. Sections
R-802.3 & R-802.10.1
- Vent eaves and roof (or gable ends),
including garages that have ceilings. Sections
R-806.1
- Trusses shall be installed and braced in
accordance with manufacturer=
s specifications. Truss members shall not be cut or
altered. Trusses shall be connected to wall plates
by use of approved connectors having a resistance to
uplift of not less than 175 pounds. Sections
R-802.10.2-R-802.10.5
- Roofing felt (No. 15) & ice water shield is
required beneath shingles. Sections R803.2 & R803.3
- Where the opening of an operable window is
located more than 72" above the finish grade, the
lowest part of the clear opening of the window shall
be a minimum of 24" above the finished floor.
Glazing between the floor and 24" shall be fixed or
have openings through which a 4" diameter sphere
cannot pass. Sections R613.2
- Cement, fiber-cement or glass mat gypsum
shall be used as backers for wall tile in tub and
shower areas. Water resistant green gypsum board is
no longer allowed in tub an shower areas. Sections
R702.4.2
- The air removed by every mechanical exhaust
system shall be discharged to the outdoors. Air
shall not be exhausted into an attic, soffit, ridge
vent or crawl space. Sections M150.1
Finish:
- Handrails - Handrails shall be provided on at
least one side of the stairways if there are 4 or
more risers and it shall have a minimum and maximum
heights of 34 to 38 inches. It shall be continuous
the full length of the stairs. Ends shall be
returned or terminated in a newel post or wall. The
maximum cross section shall not be more than 23
". This includes decks, porches and other outdoor
handrails. Sections R-311.5.6 & R-311.5.6.1
- Guardrails - Open side of stairs (including
basement stairs); and porches, balconies, and raised
floor areas located more than 30" above the floor or
grade below shall have guardrails or spindles which
will not allow passage of an object 4" or more in
diameter. Minimum height is 36" everywhere but
stairways which has a minimum of 34". Sections
R-312.1
- There shall be a floor or landing on each side
of each exterior door not more than 12
@ lower
than the top of the threshold and not more than 7:
@ below
top of the threshold. Exception: Where a stairway of
two or fewer risers is located on the exterior side
of a door, a landing is not required. Stairs from
the attached garage are interior stairs. Sections
R311.4.3
- Flashing shall be located beneath the first
course of masonry above finished ground level above
the foundation wall or slab and at other points of
support, including structural floors, shelf angles
and lintels when masonry veneers are designed in
accordance with section R703.7. See section R703.8
for additional requirements. Section R703.7.5.
Landings - A 3 x 3 landing is required on both sides
of all egress doors. Doors between the house and the
attached garage are not considered egress doors, but
the doors out of the garage area. Sections R-311.5.4
- Metal Flash the top of any exposed window (not
made with built-in flashing) or door opening, skirt
boards, stacked plywood sheet siding that is not
lapped, and any projecting trim or belt boards. This
includes 1 x 4 added over windows, doors, porches,
decks and plywood siding head joints, etc. CAULKING
IS NOT FLASHING! Sections R-703.8
- Provide a space for AIR CIRCULATION between
all roof and ceiling insulation from eaves to ridge
lines. Each space, if between rafters (sloped or
cathedral ceilings), and past the edges of blown-in
flat ceiling areas. Sections R-806.1, R-806.2 &
R-806.3
- DECKS, porches, stoops, balconies, and outside
stairways must also meet all code requirements,
including the following items. Flash between all
wood frame and concrete, above all projections and
the junction to the house. Decay resistant material
must be used anywhere within 8" of the earth or
exposure to weather. All posts must be on concrete
footings pads that rest on undisturbed earth, below
the front line and must withstand side sway. Use
joist hangers as required if less than 12
" of end bearing. Joists must be sized and spaced to
meet code, which exceeds residential floor loading
specs. Double up the end trim and notch the support
posts, or rest the joists on a beam over posts
beneath. Guard and hand rails must meet code
requirements.
February 24, 2009 * JB

|